This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section


Download 182.49 Kb.
NameThis Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section
page1/4
A typeDocumentation
manual-guide.com > manual > Documentation
  1   2   3   4

Copyright 2012 AIA MasterSpec Premium 06/12

PRODUCT MASTERSPEC LICENSED BY ARCOM TO ZURN INDUSTRIES, LLC.


Copyright 2012 by The American Institute of Architects (AIA)

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

This Product MasterSpec Section is licensed by ARCOM to Zurn Industries, LLC ("Licensee").

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section.

Revisions made to the original MasterSpec text are made solely by the Licensee and are not endorsed by, or representative of the opinions of, ARCOM or The American Institute of Architects (AIA). Neither AIA nor ARCOM are liable in any way for such revisions or for the use of this Product MasterSpec Section by any end user. A qualified design professional should review and edit the document to suit project requirements.

For more information, contact Zurn Industries, LLC, 1801 Pittsburg Ave., Erie, PA 16502; Phone: (855) ONE_ZURN; Fax: (814) 875-1402; Website: www.zurn.com; Email: zurn-info@zurn.com.

For information about MasterSpec contact ARCOM at (800) 424-5080 or visit www.MasterSpec.com.

SECTION 211100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING

Revise this Section by deleting and inserting text to meet Project-specific requirements.

This Section uses the term "Architect." Change this term to match that used to identify the design professional as defined in the General and Supplementary Conditions.

Verify that Section titles referenced in this Section are correct for this Project's Specifications; Section titles may have changed.

Lead-free statement:  Several plumbing fixtures described in this section fall under jurisdiction of the Federal Reduction of Lead in Drinking Water Act (42 USC 300G) which mandates that effective January 4, 2014 the wetted surfaces of any valve, fitting or fixture that comes in contact with potable water must have a weighted-average lead content of no more than 0.25 percent. The end user of this document is urged to be aware of the requirements of authorities having jurisdiction and to specify Lead-Free products when editing this document.  Additional information can be found online at www.zurn.com/leadfree.

PART 1 - GENERAL

1.1RELATED DOCUMENTS

Retain or delete this article in all Sections of Project Manual.

A.Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2SUMMARY

A.Section includes fire-suppression water-service piping and related components outside the building [and service entrance piping through floor into the building] [and service entrance piping through wall into the building] and the following:

1.Pipes, fittings, and specialties.

2.Fire-suppression specialty valves.

3.Concrete vaults.

4.Protective enclosures.

5.Alarm devices.

Utility companies usually provide water meters and bill charges directly or through Contractor to Owner. Contact utility company serving the site for information. Delete first paragraph below if water meters are provided by utility company or Contractor. If utility company furnishes water meters, identify the company here, specify what it does, and revise text to suit Project.

B.Utility-furnished products include water meters that are furnished to the site, ready for installation.

C.Related Requirements:

Retain subparagraphs below to cross-reference requirements Contractor might expect to find in this Section but are specified in other Sections.

1.Section 211116 "Facility Fire Hydrants" for AWWA and UL-listed, dry- and wet-barrel fire hydrants.

2.Section 211119 "Fire-Department Connections" for exposed-, flush-, and yard-type, fire-department connections.

3.Section 211200 "Fire-Suppression Standpipes" for fire-suppression standpipes inside the building.

1.3ACTION SUBMITTALS

A.Product Data: For each type of product.

B.Shop Drawings:

1.Detail precast concrete vault assemblies and indicate dimensions, method of field assembly, and components.

Retain subparagraph below if equipment includes wiring.

2.Include diagrams for power, signal, and control wiring.

1.4INFORMATIONAL SUBMITTALS

Retain "Coordination Drawings" Paragraph below for situations where limited space necessitates maximum utilization for efficient installation of different components or if coordination is required for installation of products and materials by separate installers. Preparation of coordination drawings requires the participation of each trade involved in installations within the limited space.

A.Coordination Drawings: For piping and specialties including relation to other services in same area, drawn to scale. Show piping and specialty sizes and valves, meter and specialty locations, and elevations.

B.Field quality-control reports.

1.5QUALITY ASSURANCE

Retain and revise "Regulatory Requirements" Paragraph below to suit Project, or delete if not applicable.

A.Manufacturer Qualifications: ISO 9001 registered.

Retain first paragraph below if retaining Part 2 "Trap-Seal Primer Systems" Article.

B.NSF Compliance as required by authorities having jurisdiction:

1.Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic domestic water piping components.

2.Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1 through 9."

3.Comply with NSF 372, "Drinking Water System Components - Lead Content"

C.University of Southern California Foundation for Cross-Connection Control and Hydraulic research (USC FCCCHR).

1.Manual of Cross-Connection Control.

D.Regulatory Requirements:

1.Comply with requirements of utility company supplying the water. Include tapping of water mains and backflow prevention.

2.Comply with standards of authorities having jurisdiction for fire-suppression water-service piping, including materials, hose threads, installation, and testing.

E.Piping materials shall bear label, stamp, or other markings of specified testing agency.

F.Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

G.Comply with FM Global's "Approval Guide" or UL's "Fire Protection Equipment Directory" for fire-service-main products.

H.NFPA Compliance: Comply with NFPA 24 for materials, installations, tests, flushing, and valve and hydrant supervision for fire-suppression water-service piping.

1.6DELIVERY, STORAGE, AND HANDLING

A.Preparation for Transport: Prepare valves, including fire hydrants, according to the following:

1.Ensure that valves are dry and internally protected against rust and corrosion.

2.Protect valves against damage to threaded ends and flange faces.

3.Set valves in best position for handling. Set valves closed to prevent rattling.

B.During Storage: Use precautions for valves, including fire hydrants, according to the following:

1.Do not remove end protectors unless necessary for inspection; then reinstall for storage.

2.Protect from weather. Store indoors and maintain temperature higher than ambient dew point temperature. Support off the ground or pavement in watertight enclosures when outdoor storage is necessary.

C.Handling: Use sling to handle valves and fire hydrants if size requires handling by crane or lift. Rig valves to avoid damage to exposed parts. Do not use handwheels or stems as lifting or rigging points.

D.Deliver piping with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe-end damage and to prevent entrance of dirt, debris, and moisture.

E.Protect stored piping from moisture and dirt. Elevate above grade. Do not exceed structural capacity of floor when storing inside.

F.Protect flanges, fittings, and specialties from moisture and dirt.

G.Store plastic piping protected from direct sunlight. Support to prevent sagging and bending.

1.7PROJECT CONDITIONS

Retain this article if interruption of existing water-distribution service is required.

A.Interruption of Existing Fire-Suppression Water-Service Piping: Do not interrupt service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary water-distribution service according to requirements indicated:

1.Notify [Architect] [Construction Manager] [Owner] no fewer than [two] <Insert number> days in advance of proposed interruption of service.

2.Do not proceed with interruption of service without [Architect's] [Construction Manager's] [Owner's] written permission.

PART 2 - PRODUCTS

See Editing Instruction No. 1 in the Evaluations for cautions about named manufacturers and products. For an explanation of options and Contractor's product selection procedures, see Section 016000 "Product Requirements."

First five articles below include examples of materials used for water-distribution piping. See "Writing Guide" Article in the Evaluations.

2.1COPPER TUBE AND FITTINGS

Tube in "Soft Copper Tube" Paragraph below is available in NPS 1/8 to NPS 12 (DN 6 to DN 300).

A.Soft Copper Tube: [ASTM B 88, Type K (ASTM B 88M, Type A)] [and] [ASTM B 88, Type L (ASTM B 88M, Type B)], water tube, annealed temper.

Tube in "Hard Copper Tube" Paragraph below is available in NPS 1/8 to NPS 12 (DN 6 to DN 300).

B.Hard Copper Tube: [ASTM B 88, Type K (ASTM B 88M, Type A)] [and] [ASTM B 88, Type L (ASTM B 88M, Type B)], water tube, drawn temper.

C.Copper, Solder-Joint Fittings: ASME B16.18, cast-copper-alloy or ASME B16.22, wrought-copper, solder-joint pressure type. Furnish only wrought-copper fittings if indicated.

D.Copper, Pressure-Seal Fittings:

Retain "Manufacturers" Subparagraph and list of manufacturers below to require products from manufacturers listed or a comparable product from other manufacturers.

1.Manufacturers: Subject to compliance with requirements, [provide products by the following] [provide products by one of the following] [available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following]:

a.Viega; Plumbing & Heating Systems.

b.<Insert manufacturer's name>.

2.Standard: UL 213.

3.NPS 2 (DN 50) and Smaller: Wrought-copper fitting with EPDM O-ring seal in each end.

4.NPS 2-1/2 to NPS 4 (DN 65 to DN 100): Bronze fitting with stainless-steel grip ring and EPDM O-ring seal in each end.

Flanges in "Bronze Flanges" Paragraph below are available in NPS 1/2 to NPS 12 (DN 15 to DN 300).

E.Bronze Flanges: ASME B16.24, Class 150, with solder-joint end. Furnish Class 300 flanges if required to match piping.

Unions in "Copper Unions" Paragraph below are available in NPS 1/4 to NPS 4 (DN 8 to DN 100). NFPA 13 limits unions to NPS 2 (DN 50) and smaller.

F.Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body with ball-and-socket, metal-to-metal seating surfaces, and solder-joint or threaded ends.

2.2DUCTILE-IRON PIPE AND FITTINGS

Ductile-iron pipe is intended for fire-suppression water-service-piping outside the building and underslab within the building.

Pipe in "Grooved-Joint, Ductile-Iron Pipe" Paragraph below is available in NPS 3 to NPS 24 (DN 80 to DN 600).

A.Grooved-Joint, Ductile-Iron Pipe: AWWA C151, with cut, rounded-grooved ends.

Pipe in "Mechanical-Joint, Ductile-Iron Pipe" Paragraph below is available in NPS 3 to NPS 24 (DN 80 to DN 600).

B.Mechanical-Joint, Ductile-Iron Pipe: AWWA C151, with mechanical-joint bell and plain spigot end.

Pipe in "Push-on-Joint, Ductile-Iron Pipe" Paragraph below is available in NPS 3 to NPS 48 (DN 80 to DN 1200).

C.Push-on-Joint, Ductile-Iron Pipe: AWWA C151, with push-on-joint bell and plain spigot end.

D.Grooved-End, Ductile-Iron Pipe Appurtenances:

Retain "Manufacturers" Subparagraph and list of manufacturers below to require products from manufacturers listed or a comparable product from other manufacturers.

1.Manufacturers: Subject to compliance with requirements, [provide products by the following] [provide products by one of the following] [available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following]:

a.Anvil International, Inc.

b.Corcoran Piping Systems Inc.

c.Shurjoint Piping Products.

d.Star Pipe Products.

e.Tyco Fire & Building Products LP.

f.Venus Fire Protection Ltd.

g.Victaulic Company.

h.Viking Corporation.

i.<Insert manufacturer's name>.

Fittings and couplings in "Grooved-End, Ductile-Iron Fittings" and "Grooved-End, Ductile-Iron-Piping Couplings" subparagraphs below are available in NPS 3 to NPS 24 (DN 80 to DN 600).

2.Grooved-End, Ductile-Iron Fittings: ASTM A 47/A 47M, malleable-iron castings or ASTM A 536, ductile-iron castings with dimensions matching pipe.

3.Grooved-End, Ductile-Iron-Piping Couplings: AWWA C606, for ductile-iron-pipe dimensions. Include ferrous housing sections, gasket suitable for water, and bolts and nuts.

E.Mechanical-Joint, Ductile-Iron Fittings: AWWA C110, ductile- or gray-iron standard pattern or AWWA C153, ductile-iron compact pattern.

1.Glands, Gaskets, and Bolts: AWWA C111, ductile- or gray-iron glands, rubber gaskets, and steel bolts.

Fittings in "Push-on-Joint, Ductile-Iron Fittings" Paragraph below are available in NPS 3 to NPS 48 (DN 80 to DN 1200).

F.Push-on-Joint, Ductile-Iron Fittings: AWWA C153, ductile-iron compact pattern.

1.Gaskets: AWWA C111, rubber.

Flanges in "Flanges" Paragraph below are available in NPS 1 to NPS 96 (DN 25 to DN 2400).

G.Flanges: ASME B16.1, Class 125, cast iron.

2.3PE PIPE AND FITTINGS

Pipe in "PE, Fire-Service Pipe" Paragraph below is FM Global approved in NPS 2 to NPS 12 (DN 50 to DN 300).

A.PE, Fire-Service Pipe: FM Global approved, with minimum thickness equivalent to [Class 150] [and] [Class 200].

B.Molded PE Fittings: FM Global approved; PE butt-fusion type, made to match PE pipe dimensions and class.

2.4PVC PIPE AND FITTINGS

Pipe in "PVC Pipe" Paragraph below is UL listed in NPS 4 to NPS 12 (DN 100 to DN 300).

A.PVC Pipe: [AWWA C900] [or] [UL 1285], [Class 150] [and] [Class 200], with bell end with gasket, and with spigot end.

B.PVC Fittings: [AWWA C900] [or] [UL 1285], [Class 150] [and] [Class 200], with bell-and-spigot or double-bell ends. Include elastomeric gasket in each bell.

2.5FIBERGLASS PIPE AND FITTINGS

"RTRP" is ASTM and AWWA abbreviation for fiberglass pipe; "RTRF" is ASTM abbreviation for fiberglass fittings.

Pipe in "RTRP" Paragraph below is UL listed in NPS 4 to NPS 12 (DN 100 to DN 300).

A.RTRP: UL 1713, [
  1   2   3   4

Share in:

Related:

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...

This Product MasterSpec Section modifies the original MasterSpec text, and does not include the full content of the original MasterSpec Section iconThis Product MasterSpec Section modifies the original MasterSpec...