1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards




Download 77.99 Kb.
Name1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards
page1/3
A typeDocumentation
manual-guide.com > manual > Documentation
  1   2   3
STANLEY “SCSS–700VSEC” FIRE ALARM

DISTRIBUTED VOICE/MASS NOTIFICATION SYSTEM

ENGINEER/ARCHITECT SPECIFICATION


SECTION ONE: GENERAL

1.1 Scope



This specification document provides the requirements for the installation, programming and configuration of a complete Stanley SCSS-700VSEC digital protocol analog addressable fire alarm system with distributed voice/mass notification. This system shall include, but not be limited to, system cabinet, power supply, built in Signaling Line Circuit (SLC), 160 character LCD annunciator, eight programmable Flexputs, built in dual line digital communicator associated peripheral devices, batteries, wiring, conduit and other relevant components and accessories required to furnish a complete and operational Life Safety System. SCSS-700 has the interconnection capability for up to 8 panels. The system has two modes of operation, multiple panels covering one larger building, or multiple independent buildings. SCSS-700ND is used in a networked system where at least one SCSS-700 is in the system. It is the same as an SCSS-700 without the display.

1.2 Work Included




1.2.1 General Requirements



The contractor shall furnish and install a complete 24 VDC, electrically supervised, analog addressable fire alarm system as specified herein and indicated on the drawings. The system shall include but not be limited to all control panels, power supplies, initiating devices, audible and visual notification appliances, alarm devices, and all accessories required to provide a complete operating fire alarm system.

1.2.2 Listings



All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system.

1.3 Standards



The fire alarm equipment and installation shall comply with the current provisions of the following standards and shall be listed for it’s intended purpose and be compatibility listed to insure integrity of the complete system.

1.3.1 National Electric Code, Article 760

      1. National Fire Protection Association Standards:


NFPA 70 National Electrical Code

NFPA 72 National Fire Alarm Code

NFPA 101 Life Safety Code

      1. Local and State Building Codes


BOCA, National Building Code, Mechanical Code, Fire Prevention Code

1.3.4 Local Authorities Having Jurisdiction



1.3.5 Underwriters Laboratories Inc.



All equipment shall be approved by Underwriters Laboratories, Inc. for it’s intended purpose, listed as power limited by Underwriters Laboratories, Inc., for the following standards as applicable:

UL 864 UOJZ Control units for Fire Protective Signaling Systems

Local Signaling Unit

Central Station Signaling Protected Premises Unit

Remote Signaling Protected Premises Unit.

UL 268 Smoke Detectors for Fire Protective Signaling systems.

UL 268A Smoke Detectors for duct applications

UL 217 Smoke Detectors for Single Stations

UL 521 Heat Detectors for Fire Protective Signaling systems.

UL 228 Door Holders for Fire Protective Signaling systems.

UL 464 Audible Signaling appliances

UL 1638 Visual Signaling appliances

UL 38 Manually Activated Signaling Boxes

UL 346 Waterflow indicators for Fire Protective Signaling systems.

UL 1481 Power Supplies for Fire Protective Signaling systems.

UL 2572 Communication and Control Units for Mass Notification Systems

1.3.6 Americans with Disabilities Act (ADA).



All visual Notification appliances and manual pull stations shall comply with the requirements of the Americans with Disabilities Act.

    1. General Requirements



      1. Manufacturers/Distributors Services:



        1. The following supervision shall be provided by a factory trained service technician. The technician shall be trained and shall have a minimum of two (2) years of service experience in the fire alarm industry. The technicians name shall appear on equipment submittals and a copy of his manufactures trained shall be sent to the project engineer. The technician shall be responsible for the following items:



  1. A pre installation visit to the job site to review equipment submittals and to verify the method by which the system is to be wired.

  2. During the installation the certified technician shall be on site or make periodic visits to verify installation and wiring of the system. He shall also supervise the completion of conduit rough, wires pulled into conduit and wiring rough, and ready for trim.

  3. Upon completion of wiring, final checkout and certification of the system shall be made under the supervision of this technician.

  4. At the time of the formal checkout, technician shall give operational instructions to the owner and or his representative on the system.

1.4.2 Submittals



The contractor shall submit three (3) complete sets of documentation within thirty (30) calendar days after award of the purchase order. Indicated in the document will be the type, size, rating, style, catalog number, manufacturers’ names, photos, and /or catalog data sheets for all items proposed to meet these specifications. The proposed equipment shall be subject to the approval of the Architect/Engineer and no equipment shall be ordered or installed on the premises without that approval.

NOTE: DOCUMENTATION - Submittal of shop drawings shall contain at least three (3) copies of original manufacturer specification and installation instruction sheets. Subsequent information may be copies. All equipment and devices on the shop drawings to be furnished under this contract shall be clearly marked in the specification sheets.

Suppliers’ qualifications shall be submitted indicating years in business, service policies, warranty definitions, NICET certification, and completion of factory training program and a list of similar installations.

Contractor qualifications shall be supplied indicating years in business and prior experience with installations that include the type of equipment that is to be supplied.

The contractor shall provide hourly Service Rates, performed by a factory trained technician for this installed Life Safety System with the submittal. Proof of training and authorization shall be included with the submittal. These hourly service rates shall be guaranteed for a 1-year period.

1.4.2 Contract close-out Submittals


Deliver two (2) copies of the following to the owner’s representative within Thirty (30) days of system acceptance. The closeout submittals shall include:

  1. Installation and Programming manuals for the installed Life Safety System.

  2. Point to point diagrams of the entire Life Safety System as installed. This shall include all connected Smoke Detectors and addressable field modules.

3- All drawings must reflect device address as verified in the presence of the engineer and/or end user.

1.4.3 Warranty


Warranty all materials, installation and workmanship for a one (1) year period, unless otherwise specified. A copy of the manufacturer warranty shall be provided with the close out documentation.

1.4.4 Products



This Life Safety System Specification must be conformed to in its entirety to ensure that the installed and programmed Life Safety System will accommodate all of the requirements and operations required by the building owner. Any specified item or operational feature not specifically addressed prior to the bid date will be required to be met without exception.

Submission of product purported to be equal to those specified herein will be considered as possible substitutes only when all of the following requirements have been met:

  1. Any deviation from the equipment, operations, methods, design or other criteria specified herein must be submitted in detail to the specifying Architect or Engineer a minimum of ten (10) working days prior to the scheduled submission of bids. Each deviation from the operation detailed in these specifications must be documented in detail, including page number and section number, which list the system function for which the substitution is being proposed.




  1. A complete list of such substituted products with three (3) copies of working drawings thereof shall be submitted to the approved Architect and/or Consulting Engineer not less than ten (10) working days prior to the scheduled submission of bids.



3- The contractor or substitute bidder shall functionally demonstrate that the proposed substitute products are in fact equal in quality and performance to those specified herein.
      1. General Equipment and Materials Requirements



All equipment furnished for this project shall be new and unused. All components shall be designed for uninterrupted duty. All equipment, materials, accessories, devices and other facilities covered by this specification or noted on the contract drawings and installation specification shall be best suited for the intended use and shall be provided by a single manufacturer. If any of the equipment provided under this specification is provided by different manufacturers, then that equipment shall be “Listed” as to its compatibility by Underwriters Laboratories (UL), if such compatibility is required by UL standards.

1.4.6 Satisfying the Entire Intent of these Specifications



It is the contractor’s responsibility to meet the entire intent of these specifications.

Deviations from the specified items shall be at the risk of the contractor until the date of final acceptance by the architect, engineer, and owner’s representative.

All costs for removal, relocation, or replacement of a substituted item shall be at the risk of the electrical contractor.
  1   2   3

Share in:

Related:

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards icon1 2 Labeling All fire alarm system equipment shall be listed for...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards icon1 2 Labeling All fire alarm system equipment shall be listed for...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards icon[note: listed in descending date order (latest is listed first and oldest is listed last) ]

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconFire Safety Plan – Single Stage Fire Alarm System for

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconIntelligent fire alarm detection system

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconManual release switches and the load distribution center. The Dcr...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconThis Inspection was performed in accordance with applicable standards....

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconTesting of the microprocessor controlled, intelligent reporting fire alarm equipment

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconThis document is a text description of the control panel layout for...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconThis document is a text description of the control panel layout for...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconPurpose of the System Describe why the system was created and its purpose Benefits

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconThe work in this section shall include furnishing all labor, materials,...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconAbstract Use cases are one of the uml diagram used to illustrate...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconNote: This guideline is intended to supplement normal service practice...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconBacr/bcs standards for Cardiac Rehabilitation 2002 Coding System...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards icon2. 2 Scope of system The system consists of … “for an example” the...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconManual Review of emergency procedures and equipment: Fire drill procedure,...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconCreated by the False Alarm Reduction Association (fara) and the National...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards iconAbstract Microcontroller is a basic building block for implementing...

1 2 Listings All fire alarm system equipment shall be listed for it’s intended purpose and be compatibility listed to assure the integrity of the complete system. 3 Standards icon1. System shall be a microprocessor based fully integrated lighting...




manual




When copying material provide a link © 2017
contacts
manual-guide.com
search