PCD4 Index


PCD4.A400

B




13.02.1995

20.06.1997




Typical output delay : 10 μs -– switch on delay (prior 10 μs)

50 μs -– switch off delay (prior 5 μs)
Leakage current  : max. 0.1 mA (prior 1 mA)

Version A was equipped with bipolar transistors which have a shorter switch off delay (5 μs), but a larger voltage drop (1 V at 0.5 A).

PCD4.A410

A

-1

22.12.2003

-188

TLP127-4 obsolete. Replaced by 4xTLP127




PCD4.B900




















PCD4.C130

B

-2

16.09.1993




Fitting transient suppressor diodes (10 V bidirectional) for overvoltage protection of the RS 485 interface.

SAIA® PCD Bulletin 93-3

PCD4.C225

B




19.05.1999


-112

From version “B” on, all PCD4 I/O modules with exception of H3/H4 and W1/W3/W4 (±15 V not wire) can be used.




PCD4.C340

A

-1

22.01.1998


-104

Problem : The addresses 128 and above act on the address range 0 …127 (ex. add. 160 ..167 ==> 32 …40)

Solution : Return the module for repair or insulate the path by placing a scotch between the bolt and the electronic circuit board.

Communication 98013

PCD4.H120

E

-1

03.02.1998

30.09.2002

-102

Problem : The version E doesn’t allow to use the bus terminator.

Solution : Changed silicium diodes D11 + D12 (LL4148) against Schottky diodes (LL103A)

Remark: For CPU with date 2000 .. 2002 it is recommended to have the Modification 2 realized on the CPU.

details

PCD4.H120


E




24.09.96

- 078

Improvement of the immunity, mostly on connection “-“ (Minus)




PCD4.H120

D




24.09.1993




With version “D”, the circuit has been adapted so that the bus terminator is no longer required.

From version “C” a bus terminator (4 717 4830 0) and corresponding information sheet have been enclosed with each module.




PCD4.H2x0

C




01.07.1999

-114

New controller has a new PCB (index c)

Type of the module changed to PCD4.H225 the 01.11.1999

Introduced Version C in September

PCD4.H3x1

E

-1

04.07.1999


-113

New input filter; the nominal counting frequency is guaranteed even if interruptions and start appears suddenly




PCD4.H4x0

A

-1

29.05.2000

123

Problem: No communication with the Commissioning Tool at low temperature, about 10°C

Modif. 1: Will be done on the new produced modules and on the modules returned for repair.

No call back action is necessary

PCD4.M125

PCD4.M145

PCD4.M445

B

B

C

2 8

2 8

2 8

12.05.2003


AD-EM-SBC-03-106

Problem : Not relevant for the function. One serie FCPU was mounted with pull up resistor 10k instead 4k7.

Solution : The additional“ ”"8" is put to identify this material.




PCD4.M110

PCD4.M125

PCD4.M145

PCD4.M445

K

B

B

C

12

2

2

2

30.09.2002


-131

Problem : Random rare function error due to Read error with PCD4.H120 (E or E1). Concerned CPU: Manufactured in 2000 .. 2002 with LS244 from Fairchid.

Solution : Modification of the Pull-up resistors on /Write




PCD4.M110

PCD4.M125

PCD4.M145

PCD4.M445

K

A

A

B

-1

-1

-1

-1

01.09.1999


-115

Problem : Read error with the max. of 32 E/O modules

Solution : Modification of the Pull-up resistors




PCD4.M145
(CPU 1)

A

-15

22.05.2000

-122

Problem : No communication on Port #2 and #3 (DUART 2)
(only within the temperarure range 30 to 40°C)

Solution : Put a 150 kOhm resistor in paralanufactell to the Quartz




PCD4.M170

B




10.11.2004

-135

New PCB CPU (on both sides components, no more outputs (never used, was necessary to win space) and PCB Extension to maintain ESD 6kV on D-Subs (for Ship Approval) on all types

Official in Jan 2005

PCD4.M170

A

-1

01.05.2002

-127

Pullup on IODIN 470E (before 1k)




PCD4.M445

B




21.07.1998





New Profibus-FMS firmware version V6.3

EA 050 from PCD7.F7

PCD4.N210


C

-1




096

If more than 5 x W100 the Reset stay actif and the +15 V stay low.

LED +15 V on the W100 stay off or can ligtanufachly flash.




PCD4.N210

B

-4

15.06.1996


087

Elimine les défaillances +15 V lors d’enclenchement à +30 V et basse impédance.

Corrected on vers. “C”

PCD4.N210

B




01.09.1994





New concept, ±15 V with more current

New technical caracteristics : see details in PCD4 manual




PCD4.N210

A

-12

09.12.1992


034

Make sure that with Uext 19 VDC the PCD4 starts correctly

For Germanischer Lloyd approbation

PCD4.N210

A

-1

19.12.1990




Problem : In certain installations, faults have been identified in the type of a “RESET” on the PCD4 as a result of switching motors or high power Relays, or also electrostatical discharges.

Solution : This interference can be removed by addition of a 10 nF capacitor and various connections to the circuit.




PCD4.W1x0

D

1

2000

D-034

Amplifier LM308A replaced by OPA131

TM61178/21.08.00

PCD4.W1x0

D




15.02.95

-074

Problems in production with shorts and handling

Solution: new LP index d, some resistors 0204 changed to 0805, some ceramic c 1206 changed to 0805.

TM60862/17.08.95

PCD4.W1x0

C




1990

Divers

new LP Index c

TM60504/23.04.90

PCD4.W1x0

B




1990

1017

Multiplexer IC LF13509 changes to DG509

TM60487/16.01.90

PCD4.W1x0

A

-1







Problem : Error which could be avoided by using a longer delay after changing channel selection (400 inst. of 30 μs)

Solution : This effect can be eliminated by inserting a resianufacttor.

A1 Insert 2 x 47K

B2 factory modification

C New PCB in prep.

PCD4.W3xx

D

-12

18.11.2003

-133

Problems: the converted value was too low, frequency could be too high

Solutions: new technology of integrating capacitor, other capacitors around cristal circuit




PCD4.W300

A

-1

01.11.1990




Problem . Short breaks in voltage lasting less than 1 second can hang the A/D converter, i.e. further A/D conversion is no longer possible.

Solution : A connection must be soldered between IC2 pin 39 and IC4 pin 10. The track connecting IC4 pin 10 with pin 14 must also be cut.




PCD4.W400

A

-1

27.08.1999


-116

Problem : No PCD4 startup if more than 3 x W400s are present (only for manufactoranufacturinging date 9916…992–6 - D. Gumy 18.1.2000)

Solution : Send the module to SAV only if necessary.

Communication 99081

Corrected on vers. “B”

PCD4.W500







25.04.2000


-121

New firmware version V002
It corrects also the “Working modes” problem’s (busy stay high)

Problem described in the “Communication 98071”

PCD4.W500

B

-134

07.04.2000

-120

Modifizierte Version B-1 3 muss wieder rückgängig gemacht werden auf B-1.

Beschluss TCP April: Da schon Module mit B-1 3 produziert wurden, ändert die Version auf B-1 3 4


Modif. B-1 3 4 = B-1

PCD4.W500

B

-13

08.12.1999


-117

Problem : The overvoltage protection has a too higher voltage

Solution : New serie with modification 3

Version B, Mod. 3

PCD4.W600







25.04.2000


-121

New firmware version V003
It corrects also the “Working modes” problem’s (busy stay high)

Problem described in the “Communication 98071”

PCD4.W600







01.12.1998


-110

New firmware version V002



1   2   3   4   5   6   7   8

Related:

Ea epc iconEpc software Install/Update/Uninstall Instructions




manual




When copying material provide a link © 2017
contacts
manual-guide.com
search